Three-phase overvoltage protection (three-phase modular surge arrester)
Picture show

Explanation

Three-phase overvoltage protection (three-phase modular surge arrester) is used to protect against over-voltage electrical equipment insulation protection of electrical hazards, is a new type of arrester, which is characterized in limiting overvoltage between phase while , and the effective phase overvoltage limit, which is common arrester can not be done. Protection of the vacuum switch is widely used in the rotating electric machine, parallel compensation capacitor, power plants, substations, etc., this combination is incorporated inside the protection capacity of zinc oxide varistor as the main component, it has good absorption of volt-ampere characteristics and overvoltage the ability of the protective equipment to provide reliable protection, by the power system are welcome.

Implementation of standards

This product implementation GB GB11032-2000 "metal oxide surge arresters without gaps for AC", JB/T10496-2005 "AC three-phase modular metal oxide surge arresters without gaps", ZBK49005-90 "ac systems with series MOA ", JB/T8459-1996" arrester Model methodology. "

Structural features

A novel structure unique four star connection components, technical performance, insulation resistance, high pressure, greatly reducing the use of space utilization and;
2, integrally molded composite jacket, has a good seal, explosion-proof, moisture resistant, anti-leakage trace, anti-corrosion, stain resistance, water repellency is good;
3, high voltage cable, ensure dielectric strength, flexible installation;
4, small size, light weight, saving land, particularly suitable for installation in a variety of switch cabinet (our unique product design, can be mounted vertically, but also horizontally.)

Conditions of Use
1, altitude less than 2000M;
2, ambient temperature: -40 ℃ ~ +40 ℃;
3, Power frequency: 48Hz ~ 62Hz;
4, the long-term protection on the applied frequency voltage does not exceed the continuous operating voltage protection;
5, the maximum wind speed does not exceed 35m / s;
6, earthquake intensity of 7 degrees and the following areas;
Use the Select

         The Three-phase overvoltage protection device is divided into a series with no gap and gap-type, the use of a difference is: no gap for over-voltage protection, as long as the system has over-voltage, can be well absorbed and inhibition; while gap over voltage protection, over-voltage on the system only energy reaches the breakdown voltage protection device in series so that the discharge gap, a gap-type over-voltage protection will be action.
        Therefore, in the selection of the recommended user: select None under normal conditions gap overvoltage protection, system disturbances voltage is too large or frequent division switch places choose gap overvoltage protection is appropriate.
        In order to facilitate the customer's various applications, our company has invested a large development efforts, developed a variety of combined over-voltage protection and ancillary equipment for users to choose.

Ordinary
3 ~ 35kV gapless type (indoor type and outdoor type)
Three-column (B type), four-poster (A type)
3 ~ 35kV a gap-type (indoor type and outdoor type)
Three-column (B type), four-poster (A type)
Standard cable length: 6 ~ 10kV: phase component 400mm
                                               Earth element 500mm
                                 35kV: phase component 550mm
                                          Earth element 800mm
* Cable extension when ordering
* Outdoor unworthy of high-voltage cables, for when ordering.
With phenotypes (characteristic suffix letter "B")
3 ~ 35kV indoor type overvoltage protector base inlaid miniature discharge counter (model suffix characteristic letter "BF")
3 ~ 35kV indoor type voltage protection and over-voltage detector combined with (panel mounting, also shows the year, month, day, hour, minute, and the relative number of operations, 30 sets of data stored in computer chips. (Part number suffix features the letters "BJ")
3 ~ 35kV outdoor voltage protection and over-voltage line monitoring of incidental or discharge counter (model suffix characteristic letter "BJ" or "BF")
Explosion-proof (characteristic letter suffix "KY")                                     High capacity type
Explosion-proof over-voltage protection (indoor type and outdoor type) in over-voltage protection fault in the installation from the device, when the over-voltage protection device fails fails, the protector from the device and the system automatically de-brain, to avoid explosion . Overvoltage protection and explosion-proof supporting the counter is JSZ-8 fault indication type discharge counter, it can give the normal and fault indication.
High-capacity type can withstand 600 ~ 800A square wave flow capacity.
Model comparison table
       Currently Three-phase overvoltage protection device is in the older models with the national standard JB/T8459-1996 "arrester Model Methods" models of the transitional period, in order to facilitate the majority of users of the products purchased reasonable selection, avoid the use of misunderstanding the product, the company now two models and uses listed in the table for the user to refer to the use.
  System voltage
kV
National Standard Model At present the common part of the old models Use of the product spaces
Outdoor suffix "W"
No gap 6 HY5WZ-10/27×2 TBP-A-     TCB-Z-     TDP-A-     TBP-O-
TBP-B-     TCB-R-     TDP-B-
TBP-C-     TCB-D-     TDP-C-


BOD-A-     KY2-A-     BOG-A-
BOD-B-     KY2-B-     BOG-B-
BOD-C-     KY2-C-     BOG-C-


DGB-S-     JPBHY5CZ1-
DGB-M-     JPBHY5CZ2-
DGB-R-
DGB-Z-



High capacity type:BSTG     SKB
Station type
10 YH5WZ-17/45×2
35 YH5WZ-51/150×51/134
6 YH5WR-10/27×2 Parallel compensation capacitor bank
10 YH5WR-17/45×2
35 YH5WR-51/150×51/134
6.3 YH2.5WD-8/25×8/19 Electric motor Protection of rotating electrical machines
10.5 YH2.5WD-13.5/38.7×13.5/31
6.3 YH5WD-8/25×8/19 Generator
10.5 YH5WD-13.5/38.7×13.5/31
13.8 YH5WD-17.5/53×17.5/40
6.3 YH1.5WD-4.8/12 Motor neutral point
10.5 YH1.5WD-8/19
Gap 6 YH5CZ-7.6/22×2 Station type
10 YH5CZ-12.7/38×2
35 YH5CZ-51/116×2
6 YH5CR-7.6/27×2 Parallel compensation capacitor bank
10 YH5CR-12.7/38×2
35 YH5CR-51/116×2
6.3 YH2.5CD-7.6/17×2 Generator Protection of rotating electrical machines
10.5 YH2.5CD-12.7/29×2
6.3 YH5CD-7.6/17×2 Motor neutral point
10.5 YH5CD-12.7/29×2
13.8 YH5CD-17.5/36×2
6.3 YH1.5CD-4.8/8.5 Motor neutral point
10.5 YH1.5CD-8/12
No gap overvoltage protection Specifications
System rated voltage
kV
Protection rated voltage
kV
Wiring Continuous operating voltage DC reference voltage U1mA
≮kV
Frequency reference voltage
≮kV
Residual voltage at nominal discharge current
≯kV
2msSquare-wave current impulse withstand
≮kV
Remark
6 10 Phase - phase 8.0 15.0 11.5 27 200 Station type
Phase - ground 14.4 10.0 27
10 17 Phase - phase 13.6 25.0 18.0 45 200
Phase - ground 24.0 17.0 45
35 51 Phase - phase 40.8 88.0 59.0 150 200
Phase - ground 73.0 51.0 134
6 10 Phase - phase 8.0 15.0 11.0 27 400 Parallel compensation capacitor bank
Phase - ground 13.8 10.0 27
10 17 Phase - phase 13.6 25.0 18.0 45 400
Phase - ground 23.0 17.0 45
35 51 Phase - phase 40.8 88.0 59.0 150 400
Phase - ground 73.0 51.0 134
6.3 8.0 Phase - phase 6.9 15.0 10.0 23.3 400 Rotary motor protection
Phase - ground 11.3 8.0 18.7
10.5 13.5 Phase - phase 11.5 24.0 16.5 38.7 400
Phase - ground 18.9 13.5 31
6.3 8.0 Phase - phase 6.9 15.0 10.0 23.3 400 Protection of rotating generators
Phase - ground 11.3 8.0 18.7
10.5 13.5 Phase - phase 11.5 24.0 16.5 38.7 400
Phase - ground 18.9 13.5 31
13.8 17.5 Phase - phase 13.8 26.0 21.5 53 400
Phase - ground 21.0 17.5 40
6.3 4.8 Phase - ground 3.8 6.8 4.8 12 250 Motor neutral point protection
10.5 8.0 Phase - ground 6.4 11.4 8.0 19 250
Gap-type over-voltage protection Technical parameters
System rated voltage
kV
Arrester rated voltage
kV
Wiring 1.2/50μs Impulse discharge voltage
≯kV
Frequency discharge voltage
≮kV
Residual voltage at nominal discharge current
≯kV
2ms Square-wave current impulse withstand
≮kV
Remark
6 7.6 Phase-phase 24.0 16.0 24.0 400 Station type
Phase-ground
10 12.7 Phase-phase 41.0 26.0 41.0 400
Phase-ground
35 42 Phase-phase 124.0 80.0 124.0 400
Phase-ground
6 7.6 Phase-phase 24.0 16.0 24.0 400 Parallel compensation capacitor bank
Phase-ground
10 12.7 Phase-phase 41.0 26.0 41.0 400
Phase-ground
35 42 Phase-phase 124.0 80.0 124.0 400
Phase-ground
6.3 7.6 Phase-phase 18.7 15.0 18.7 400 Rotary motor protection
Phase-ground
10.5 12.7 Phase-phase 31.0 25.0 31.0 400
Phase-ground
6.3 7.6 Phase-phase 18.7 15.0 18.7 400 Protection of rotating generators
Phase-ground
10.5 12.7 Phase-phase 31.0 25.0 31.0 400
Phase-ground
6.3 4.8 Phase-ground 12.0 9.0 10 250 Motor neutral point protection
10.5 8.0 Phase-ground 19.0 15.0 16